Parameterization
72/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
If you want to change the “Reading refresh rate” of the device from
100
ms
(default) to
200
ms
, you have to set Bit 4 to FALSE and Bit 5 to TRUE (see
table
Bit assignment of parameter byte of EU5E-SWD-4AX
on page 66):
Bit 0 (Sensor selector input 1)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 1 (Sensor selector input 2)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 2 (Sensor selector input 3)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 3 (Sensor selector input 4)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 4 (Reading refresh rate)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 5 (Reading refresh rate)
=
TRUE
(1)
=
32
(Dez)
=
0x20
(Hex)
+
Bit 6 (Mean value/averaging)
=
TRUE
(1)
=
64
(Dez)
=
0x40
(Hex)
+
Bit 7 (Reserved)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
=
Parameter Byte
96
(Dez)
=
0x60
(Hex)
0x60
thus is the value you have to enter as parameter byte for the device
in TwinCAT.