Firmware recovery
34/63
8.2
Using an SD memory card to reset the netTAP to its “factory
settings”
The netTAP
NT 151-CCIES-RE
can be reset to its factory settings by using
the load memory image on an SD memory card. You will find the load
memory image on the Gateway Solutions DVD in the
Supplements &
Examples\Device Factory Reset\netTAP 151 CCLINK IE
Factory Settings\Recovery via Memory Card
directory. From
there, you can copy the image to the SD memory card, and then use the
card to copy it to the netTAP device.
All existing old data (including the configuration) in the internal load
memory of the netTAP will thereby be deleted and a “base firmware” will be
loaded to the device. After recovery by SD card, you therefore must
download the full “regular” firmware and a new configuration to the device
with SYCON.net.
Note:
The SD memory card is not included in the delivery of the
NT 151-
CCIES-RE
device, but can be obtained from Hilscher. The part
number of the card is 1719.003.
Prerequisites
·
Empty SD memory card (FAT formatted)
·
PC with SD card reader device
·
Gateway Solutions DVD
·
The netTAP device is supplied with voltage
Step-by-step instructions
1. Copy load memory image from DVD to SD card.
Ø
If applicable: remove write protection on your SD memory card.
Ø
Insert the empty SD memory card into the SD card reader device of
your PC.
Ø
On the Gateway Solutions DVD, open
Supplements & Examples
\Device Factory Reset\netTAP 151 CCLINK IE Factory
Settings\Recovery via Memory Card
directory.
Ø
Copy the
STARTUP.INI
file and the
BACKUP
folder (with all its
subfolders) to the root directory of the SD memory card.
Ø
Remove the SD memory card from the SD card reader device.
netTAP NT 151-CCIES-RE | CC-Link IE Field Slave to PROFINET IO-Device gateway
DOC180403UM01EN | Revision 1 | English | 2018-08 | Released | Public
© Hilscher 2018