Firmware recovery
35/63
2. Copy load memory image to netTAP device.
Ø
Disconnect the voltage supply from your netTAP device.
Ø
Insert the SD card into the card slot of the netTAP device until it
engages (metal contacts of the card must be facing left).
Figure 7: Insert SD card
Ø
Reconnect the voltage supply of your netTAP device.
Ê
The device then loads the memory image. While loading the image, the
SYS
LED quickly alternates between green and yellow for
approximately eight seconds, then shows steady yellow for
approximately ten seconds, then is switched off for a short while before
it finally shows steady green light. The device automatically starts the
loaded firmware.
Ø
Remove the SD memory card from device.
ð
The netTAP device has been reset to its factory settings.
The device now needs a firmware download and a new configuration
with SYCON.net via USB connection. Instructions for this can be found
in the operating instruction manual
Configuration of Gateway and Proxy
Devices
, DOC081201OIxxEN.
netTAP NT 151-CCIES-RE | CC-Link IE Field Slave to PROFINET IO-Device gateway
DOC180403UM01EN | Revision 1 | English | 2018-08 | Released | Public
© Hilscher 2018