LEDs
52/63
10.3 APL LED
The APL LED indicates the communication state between CC-Link IE Field
Slave (X2) and the PROFINET IO-Device (X3), as well as the configuration
state of the device.
LED
Color
State
Meaning
APL
Position in the
device drawing:
(6)
Duo-LED red/green
(green)
on
The communication on X2 and X3 is in cyclic data exchange and the
gateway function is executed.
(green)
Blinking with
1 s on,
1 s off
(0.5 Hz)
netTAP is initialized, but has detected some error or both networks are
not connected.
(green)
Blinking with
2 s off,
0.5 s on
netTAP is initialized, but the communication on X2 is not in cyclic data
exchange.
(green)
Blinking with
2 s off,
0.5 s on,
0.5 s off,
0.5 s on
netTAP is initialized, but the communication on X3 is not in cyclic data
exchange.
(red)
Blinking with
2 s off,
0.5 s on
netTAP is initialized, but the configuration for the communication
protocol on X2 is missing or has an error.
(red)
Blinking with
2 s off,
0.5 s on,
0.5 s off,
0.5 s on
netTAP is initialized, but the configuration for the communication
protocol on X3 is missing or has an error.
(red)
On
netTAP has detected an error during the initialization:
·
Missing configuration
·
Error in configuration
·
Internal error
Table 17: APL LED