Technical data
250/263
17.2 Technical data PROFINET IO Device
Parameter
Description
Maximum number of cyclic input data
1440 Bytes
Maximum number of cyclic output data
1440 Bytes
Maximum number of submodules
255 submodules per Application Relation at the same time, 1000
submodules can be configured
Multiple Application Relations (AR)
The Stack can handle up to 2 IO-ARs, one Supervisor AR and one
Supervisor-DA AR at the same time.
Supported protocols
RTC – Real Time Cyclic Protocol, Class 1 (unsynchronized), Class 3
(synchronized)
RTA – Real Time Acyclic Protocol
DCP – Discovery and configuration Protocol
CL-RPC – Connectionless Remote Procedure Call
LLDP – Link Layer Discovery Protocol
SNMP – Simple Network Management Protocol
MRP – MRP Client
Topology recognition
LLDP, SNMP V1, MIB2, physical device
Identification & Maintenance
Read and write of I&M1-4
Minimum cycle time
1 ms for RT_CLASS_1
250 µs for RT_CLASS_3
IRT Support
RT_CLASS_3
Media redundancy
MRP client is supported
Additional features
DCP, VLAN- and priority-tagging, Shared Device
Baud rate
100 MBit/s
Data transport layer
Ethernet II, IEEE 802.3
PROFINET IO specification
V2.2 (legacy startup) and V2.3 (but advanced startup only for RT) are
supported.
Limitations
RT over UDP not supported.
Multicast communication not supported.
DHCP is not supported.
FastStartUp is not supported.
The amount of configured IO-data influences the minimum cycle time that
can be reached.
Only 1 Input-CR and 1 Output-CR are supported.
Using little endian (LSB-MSB) byte order for cyclic process data instead of
default big endian (MSB-LSB) byte order may have a negative impact on
minimum reachable cycle time.
System Redundancy (SR-AR) and Configuration-in-Run (CiR) are not
supported.
Max. 255 submodules can be used simultaneously within one specific
Application Relation.
Advanced Startup according Profinet specification V2.3 is NOT yet supported
for IRT.
As there is no official certification available for Profinet IO specification V2.3
at the time of release of the stack there is no guarantee that this
implementation will pass such a certification once it is available.
Reference to stack version
V3.9
Table 77: Technical data PROFINET IO RT IRT Device Protocol
Edge Gateway | NIOT-E-TIB100-GB-RE (Remote)
DOC170501UM04EN | Revision 4 | English | 2018-08 | Released | Public
© Hilscher 2017 – 2018