220
08/2018
www.hilti.group
S-BT-ER, S-BT-EF
Installation
Single point connection
Single point connection type A:
Upper nut
Lock washer
Cable lug
Bottom nut
Single point connection type B:
Lock washer
Cable lug
Coated
base material
Conductivity
disc
Uncoated
base material
Nut
Sealing ring
For Type B cable connection the following requirements have to be observed:
• The conductivity disc must be in direct contact with the non-coated base material.
Coating has to be removed with the coating removal drill bit.
•
Tightening torque of 8 Nm
must be observed accurately.