S-BT-ER, S-BT-EF
08/2018
211
www.hilti.group
For discharging short circuit current while protecting electrical equipment or earth / ground
cable trays and ladders.
Protective bonding circuit
Double point connection
Single point connection
Note:
• Recommended maximal cross section of connected cable
according
IEC 60947-7-2 and IEC 60947-7-1:
10 mm² (8 AWG) copper (tested short circuit current I
cw
= 1.20 kA for 1 s)
35 mm² (2 AWG) copper (tested short circuit current I
cw
= 4.20 kA for 1 s)
120 mm² (4/0 AWG) copper (tested short circuit current I
cw
= 14.40 kA for 1 s)
according
UL 467
:
10 AWG copper (tested short circuit current I
cw
= 0.75 kA for 4 s)
2 AWG copper (tested short circuit current I
cw
= 3.90 kA for 6 s)
4/0 AWG copper (tested short circuit current I
cw
= 10.10 kA for 9 s)
• Fastening of thicker cable is acceptable, if the maximum short circuit current
I
cw
and the exposure time is not exceeded and the provisions on cable lug thickness
t
cl
are observed.
Recommended electrical
connectors:
S-BT-ER M10/15 SN 6
S-BT-ER W10/15 SN 6
S-BT-EF M10/15 AN 6
S-BT-EF W10/15 AN 6
S-BT-ER M8/15 SN 6
S-BT-EF M8/15 AN 6
S-BT-ER M10 HC 35*)
S-BT-ER W10 HC AWG2*)
S-BT-EF M10 HC 35*)
S-BT-EF W10 HC AWG2*)
S-BT-ER M10 HC 120
S-BT-ER W10 HC AWG4/0
S-BT-EF M10 HC 120
S-BT-EF W10 HC AWG4/0
Recommended electrical
connectors:
S-BT-ER M10/15 SN 6
S-BT-ER W10/15 SN 6
S-BT-EF M10/15 AN 6
S-BT-EF W10/15 AN 6
S-BT-ER M8/15 SN 6
S-BT-EF M8/15 AN 6
Max. short circuit current
according to IEC and UL
Icw = 1.20 kA (IEC)
Icw = 0.75 kA (UL)
Icw = 4.20 kA (IEC)
Icw = 3.90 kA (UL)
Icw = 14.40 kA (IEC)
Icw = 10.10 kA (UL)
Type A
Type B
Type A
Max. short circuit current
according to IEC
Icw = 1.92 kA (IEC)
*) this items are available only on special request