4 Start-Up
DIO 24/16 01
Page 22 of 40
HI 800 205 E Rev. 1.01
4.3.1
Parameters and Error Codes for the Inputs and Outputs
The following tables specify the system parameters that can be read and set for the inputs
and outputs, including the corresponding error codes.
In the user program, the error codes can be read using the variables assigned within the
logic.
The error codes can also be displayed in SILworX.
4.3.2
Digital Inputs and Outputs
The following tables present the statuses and parameters for the input and the output
module in the same order as given in the Hardware Editor.
4.3.2.1
Module
Tab
The
Module
tab contains the following system parameters.
System parameter
Data type R/W
Description
DI Number of Pulsed
Channels
USINT
W
Number of pulsed outputs (supply outputs)
Coding
Description
0
No output planned for LS/LB
1)
detection
1
Output channel 1 planned for LS/LB
1)
detection
2
Output channels 1...2 planned for LS/LB
1)
detection
… …
8
Output channels 1...8 planned for LS/LB
1)
detection
Pulsed outputs must not be used as safety-related outputs!
DI Pulse
Slot
UDINT W Pulse module slot: Value 1...6, according to the actual slot
on the right of the CPU
DI Pulse Delay (10E-
6s)
UINT W Waiting time for line control (detection of short-circuits or
cross-circuits)
DI.Error Code
WORD
R
Error codes for all digital inputs
Coding
Description
0x0001 Module
fault
0x0002
FTT test of test pattern faulty