DIO 24/16 01
4 Start-Up
HI 800 205 E Rev. 1.01
Page 25 of 40
4.4
Configuring a Module Using ELOP II Factory
4.4.1 Configuring
the Inputs and Outputs
The signals previously defined in the Signal Editor (Hardware Management) are assigned
to the individual channels (inputs and outputs) using ELOP II Factory. Refer to the System
Manual for Compact Systems or the online help for more details
The following chapter describes the system signals used for assigning signals in the
controller.
4.4.2
Signals and Error Codes for the Inputs and Outputs
The following tables specify the system signals that can be read and set for the inputs and
outputs, including the corresponding error codes.
In the user program, the error codes can be read using the signals assigned within the
logic.
The error codes can also be displayed in ELOP II Factory.
4.4.3 Digital
Inputs
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0xFE01 [65025
dec
]
Mod. Error Code
[WORD]
R
Error codes for the module
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DI.Error Code
[WORD]
R
Error codes for all digital inputs
Coding
Description
0x0001 Module
fault
0x0002
FTT test of test pattern faulty
DI[xx].Error Code
[BYTE]
R
Error codes for the digital input channels
Coding
Description
0x01
Fault in the digital input module
0x10
Short-circuit of the channel
0x80
Intermittence between pulsed output DO and digital
input DI, e.g.,
Open-circuit
Open
switch
L+ low voltage