To ensure high availability, operate the HIQuad X systems as follows:
Use redundant power supplies.
The power supply units or the 24 VDC power nets must ensure the output voltage never
exceeds 31 V.
Use suitable fuses in the fuse and power distribution module to limit the maximum current
input in each base rack to 16 A.
Users must implement external measures to ensure that the power supply does not fall
below 0.8 x U
N
(= 19.2 VDC). If no redundant power supply is available, the system
responds with failure of individual components or the entire system.
The power distribution modules, K 7205, K 7212, K 7213 and K 7214, include all components
required to secure up to 18 individual circuits with circuit breakers. The K 7212 set is additionally
equipped with decoupling diodes and mains filters with monitoring relays.