4.7
Modules
The HIQuad X system is a modular system that can be equipped with various modules. The
following modules are available for the system:
F-CPU 01 processor module
F-IOP 01 I/O processing module
F-COM 01 communication module
I/O modules, see Chapter 4.11
F-PWR 01 power supply unit (24/5 V)
F-PWR 02 buffer module
4.8
F-CPU 01 Processor Module
The CPU operating system controls the user programs running in a processor module.
4.8.1
Operating System
Tasks:
Controlling the cyclic run of the user programs.
Performing the self-tests of the module.
Controlling safety-related communication via safe
ethernet.
Managing the processor modules' redundancy (synchronization).
4.8.1.1
General Cycle Sequence
Phases:
1. Reading of the input data.
2. Processing of the user program.
3. Writing of the output data.
4. Other activities, e.g., reload processing.
4.8.1.2
Operating System States
States that can be recognized by the user:
LOCKED
STOP/VALID CONFIGURATION
STOP/INVALID CONFIGURATION
STOP/LOADING OS
RUN
RUN/UP STOP
Use the LEDs on the module to recognize the operating state. All LEDs must be taken into
account, see the module-specific manuals.
SILworX displays the operating states in the online view.
Summary of Contents for HIQuad H41X
Page 1: ...Manual HIQuad X System Manual...