System
Product Data, Dimensioning
HI 803 211 E Rev. 1.01.00
Page 93 of 110
8
Product Data, Dimensioning
This chapter specifies the environmental requirements and the dimensions to be set in the
SILworX programming tool.
8.1
Environmental Conditions
Exposing the HIQuad X system to environmental conditions other than those indicated can
cause it to malfunction. Additionally, the instructions provided in the module-specific manuals
must be observed.
General
Protection class
Protection class II in accordance with IEC/EN 61131-2
Ambient temperature
0…+60 °C
Transport and storage
temperature
-
40…+70 °C
Pollution
Pollution degree II
Altitude
< 2000 m
Enclosure
Standard: IP20
If required by the relevant application standards (e.g.,
EN 60204), the system must be installed in an enclosure with
the specified degree of protection (e.g., IP54).
Power Supply Input Voltage
24 VDC, -15...+20 %, r
p
≤ 5 %
SELV, PELV
Table 34: Environmental Conditions
8.2
Dimensioning
For details, refer to the component-specific manuals and communication manual
(HI 801 101 E).
For each resource
Value
Number of racks
H51X: 1 base rack and a maximum of
16 extension racks.
H41X: 1 base rack and a maximum of 1
extension rack.
Number of I/O modules
H51X: 256
H41X: 28 (with extension rack)
Number of I/O elements
Depending on the module type
H51X: 4096
H41X: 224
Number of processor modules
2
Total program and data memory for all user
programs
5 MB less 64 kB for CRCs
Memory for retain variables
32
Number of I/O processing modules for each rack
1 (none in the H51X base rack)
Maximum length of the system buses
50 m between two subscribers.
Number of communication modules
H51X: 0…10
H41X: 0…2
Puffergröße für Verbindung zum OPC-Server
Anzahl PES-Benutzergruppen
1…10
Anzahl Anwenderprogramme
1…32
Anzahl Ereignisdefinitionen
0…5000
Größe des nichtflüchtigen Ereignispuffers
1000 Events
Table 35: Dimensioning of a HIQuad X Controller