Product Description
System
Page 32 of 110
HI 803 211 E Rev. 1.01.00
4.2.1.2
Buffered Voltage for LS1+ and LS2+ in F-PWR 02 Buffer Modules
The buffered voltage (LS1+ or LS2+) for extension racks is connected to the following terminals:
Spring terminal
Cross-section and color
XG7.1 (LS2-)
2.5 mm² BK
XG7.2 (LS2+)
2.5 mm² RD
XG7.3 (LS1-)
2.5 mm² BK
XG7.4 (LS1+)
2.5 mm² RD
Table 8:
Spring Terminals for Buffered Voltage
4.2.1.3
5 V Power Supply for Extension Racks
The 5 V power supply for extension racks is connected to the following terminals:
Spring terminal
Cross-section and color
XG2.1…XG2.13 (Vcc)
2.5 mm² YE
XG3.1
…XG3.13 (Vcc)
2.5 mm² YE
XG4.1
…XG4.13 (GND)
2.5 mm² GN
XG5.1
…XG5.13 (GND)
2.5 mm² GN
Table 9:
Spring Terminals for 5 V Power Supply
4.2.1.4
Signaling Relay for F-PWR 02 Buffer Module, XG6
The signaling relay in the buffer modules is connected to the following terminals:
Spring terminal
Cross-section and color
XG6.1…XG6.3 (REL2)
2.5 mm² GR
XG6.4…XG6.6 (REL1)
2.5 mm² GR
Table 10: Spring Terminals in 5 Signaling Relays for Buffer Module