X-AI 32 51
3 Product Description
HI 801 181 E Rev. 4.00
Page 27 of 58
3.7 System
Cable
The system cables are used to connect the connector boards to the field zone via field
termination assemblies.
Identical Cable Plugs
Figure 9:
System Cable
Depending on the type of connector board, two different types of system cables are
available.
3.7.1
System Cable X-CA 005
The X-CA 005 system cable is used to connect the X-CB 008 53/54/57 and
X-CB 019 53/54 connector boards to the field zone via field termination assemblies or inline
terminals.
General
Cable
LIYCY-TP 38 x 2 x 0.25 mm²
Wire
Finely stranded
Average outer diameter (d)
approx. 16.8 mm
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length 5…30
m
Color coding
Based on DIN 47100, see Table 15.
Table 17: Cable Data X-CA 005