4 Start-up
X-DO 24 02
Page 38 of 54
HI 801 095 E Rev. 4.00
4.4.4 Submodule
Status [DWORD]
Coding of
Submodule Status
Coding
Description
0x00000001
Fault in hardware unit (submodule).
0x00000002
Reset of an I/O bus
0x00000004
Fault detected while configuring the hardware
0x00000008
Fault detected while verifying the coefficients
0x00000010
First temperature threshold exceeded (warning temperature)
0x00000020
Second temperature threshold exceeded (limit temperature)
0x00000040
Overcurrent, module shutdown
0x00000080
Reset of CS monitoring (Chip Select monitoring)
0x00000100
Line monitoring hardware fault
0x00800000
Voltage monitoring of WD1: voltage error
0x01000000
Voltage monitoring of WD2: voltage error
0x02000000
Voltage monitoring of L1+ HIGH voltage defective
0x04000000
Voltage monitoring of L1+ LOW voltage defective
0x08000000
Voltage monitoring of L2+ HIGH voltage defective
0x10000000
Voltage monitoring of L2+ LOW voltage defective
0x20000000
Voltage monitoring of AGND voltage defective
0x40000000
Voltage monitoring of VMOS HIGH voltage defective
0x80000000
Voltage monitoring of VMOS LOW voltage defective
Table 20: Submodule Status [DWORD]