Alarms
50
/
52
42
Excess
position
deviation
Value of
deviation
counter
exceeded the
specified
value
Occurs at pulse
command input
Pulse was input without
turning servo ON
Check the servo ON
signal
The F-LMT and R-LMT
signals are not input or
configured
Check the wiring and
settings
Occurs when
accelerating/decelera
ting
Acceleration/deceleration
speed is too high
Reduce the
acceleration/deceleration
speed
Error list (motor driver errors)
Error
No.
Name
Description
Status
Cause
Solution
51
Over heat
Abnormal
temperature
of power
drive was
detected
Occurs while in
operation
Frequent use while
overloaded
Relax the operating
conditions
Ambient temperature is
high
Install a fan or other
device to improve heat
dissipation
61
Sensor Error
Sensor error
When power is
turned ON
Detected small amplitude
of resolver signal
Turn up the sensor
excitation voltage one step
62
Detected excessively
large amplitude of
resolver signal
Turn down the sensor
excitation voltage one step
71
Over Voltage
Excess drive
voltage
Occurs while in
operation
Insufficient regeneration
ability
Insufficient power supply
capacity:
Add regeneration
protection circuit to power
supply/
Insufficient regeneration
protection ability:
Reduce the deceleration
speed
Occurs when power
is turned ON
If detected when power is
turned ON, the voltage
specifications are not
suitable.
Change the driver
Driver failure
Replace driver
Sometimes detected
when using
Driver detects voltage of
regeneration protection
Increase the value of
ID205 "Excess voltage
Summary of Contents for DCD-40L
Page 1: ...Current Controlled Screwdriver DCD 40L 115W Instruction Manual ET A070 19A HIOS Inc ...
Page 27: ... Operation timing charts 27 52 Pattern 2 ...
Page 28: ... Operation timing charts 28 52 Pattern 3 ...
Page 29: ... Operation timing charts 29 52 Pattern 4 ...
Page 37: ... I O 37 52 Timing chart for normal operations when torque judgment is NG ...
Page 38: ... I O 38 52 Timing chart when emergency stop signal is input ...