8
BAT-F, BAT-Rail, BAT54, BAT300
Release 02 07/10
Install the device in a location where the climatic threshold values
specified in the technical data will be observed.
Use the device only in an environment within the contamination level
specified in the technical data.
When installing external antennas, adhere to the regulations of the
country in which you are operating the WLAN device.
In ambient temperatures under -10 °C, use cabling designed for
minimum temperatures.
Relevant for use in Ex zone 2 according to ATEX 95 (ATEX 100a):
Only products labeled accordingly may be operated in Ex zone 2.
When operating the BAT-F X2 types in Ex zone 2, the following applies:
II 3G
Ex nA II T4 -20°C ... +60°C
KEMA 07 ATEX 0190
DO NOT OPEN THE DEVICE WHEN IT IS ELECTRICALLY CHARGED.
DO NOT DETACH ANY CONNECTORS WHEN THE DEVICE IS
ELECTRICALLY CHARGED.
DO NOT REMOVE THE LABELED HOUSING COVER.
The BAT-F X2 (FCC) types are installed with a housing cover - as
mounted in the state on delivery.
Lightning protection
When you mount devices and / or antennas outdoors, there is a risk of
them being struck by lightning. Additionally, there is the risk of voltage
surges being transmitted into the interior of the building. It is your
responsibility to take appropriate measures to mitigate the effects of
lightning strikes. Make sure the equipment is installed by a licensed
electrician in accordance with local, regional and national regulations for
codes and standards (such as VDE 0182 and IEC 62305) and according
to best practices for your application and environment.
Temperature Code T4
Ambient –20 °C … +60 °C
List of Standards
EN 60079-0: 2006
EN 60079-15: 2005
CLC/TR 50427: Dez. 2004