28
Installation
GREYHOUND Media Modu
le
s
Re
lease
01
11/2
014
EMC and immunity
EMC interference
emission
Standard
applications
a
a. EN 61131-2, CE, FCC – applies to all devices
Merchant Navy
b
b. Merchant Navy – applies to devices with the approval codes U9, UT, UX, UY, VU
Railway
applications
(trackside)
c
c. EN 50121-4 – applies to devices with the certification codes VT, T9, TY
Substation
applications
d
d. EN 61850-3, IEEE 1613 – applies to devices with the certification codes V9, VY, VU, VT
Radiated emission
EN 55022
Class A
Class A
Class A
Class A
GL Guidelines
—
EMC 1
—
—
FCC 47 CFR Part 15
Class A
Class A
Class A
Class A
EN 61000-6-4
Fulfilled
Fulfilled
Fulfilled
Fulfilled
Conducted emission
EN 55022
DC supply connection
Class A
Class A
Class A
Class A
GL Guidelines
DC supply connection
—
EMC 1
—
—
FCC 47 CFR Part 15
DC supply connection
Class A
Class A
Class A
Class A
EN 61000-6-4
DC supply connection
Fulfilled
Fulfilled
Fulfilled
Fulfilled
EN 55022
Telecommunication connections
Class A
Class A
Class A
Class A
EN 61000-6-4
Telecommunication connections
Fulfilled
Fulfilled
Fulfilled
Fulfilled
EMC interference
immunity
Standard
applications
a
Merchant Navy
b
Railway
applications
(trackside)
c
Substation
applications
d
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
± 4 kV
± 6 kV
± 6 kV
± 8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
± 8 kV
± 8 kV
± 8 kV
± 15 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 3000 MHz
10 V/m
10 V/m
20 V/m
10 V/m