background image

6

5. Technical data

General data

Operating voltage

NEC Class 2 power source 9.6 VDC … 32.0 VDC safety extra-low voltage (SELV/PELV) 
5 A maximum

Buffer time

min. 10 ms at 20.4 VDC

Potential difference between input

Potential difference to input voltage, +24 VDC: 32 VDC

voltage and housing

Potential difference to input voltage, ground: -32 VDC

Current consumption at 24 VDC

2.2 W maximum;  7.5 Btu (IT)/h

SPIDER 5TX

3.9 W maximum;  13.3 Btu (IT)/h

SPIDER 8TX

3.9 W maximum;  13.3 Btu (IT)/h

SPIDER 4TX/1FX

Dimensions W x H x D

25 mm x 114 mm x 79 mm

1.0 in x 4.5 in x 3.2 in

SPIDER 5TX

40 mm x 114 mm x 79 mm

1.6 in x 4.5 in x 3.2 in

SPIDER 8TX

25 mm x 114 mm x 79 mm

1.0 in x 4.5 in x 3.2 in

SPIDER 4TX/1FX

Weight

113 g

0.25 lb

SPIDER 5TX

177 g

0.39 lb

SPIDER 8TX

120 g

0.27 lb

SPIDER 4TX/1FX

Ambient temperature

Surrounding air 0 ºC to + 60 ºC

32 ºF to 140 ºF

Storage temperature

Surrounding air - 40 ºC to + 70 ºC

-40 ºF to 158 ºF

Humidity

up to 95% (non condensing)

Atmospheric pressure

up to 2000 m (795 hPa, higher altitudes on demand)

Pollution Degree

2

Protection type

IP 30

Interference proof

Discharge of static electricity

Contact discharge

EN 61000-4-2 Test level 3

Air discharge

EN 61000-4-2 Test level 3

Electromagnetic fields

EN 61000-4-3 Test level 3

Fast transients

EN 61000-4-4 Test level 3

Surge voltage symmetrical

EN 61000-4-5 Test level 2

Surge voltage asymmetrical

EN 61000-4-5 Test level 3

Cable-based RF faults

EN 61000-4-6 Test level 3

Fig. 5: Assembling the SPIDER xTX(/xFX)

Fig. 6: Dimensions 

13,7

70

63,3

23

8,5

3.3 STARTUP PROCEDURE

You start up the SPIDER xTX(/xFX) by

connecting the supply voltage via the 3-pin
terminal block.

3.4 DISMANTLING

To take the SPIDER xTX(/xFX) off the

ISO/DIN rail, unlock the snap-in mechanism
according to Fig 7.

Fig. 7: Dismantling the SPIDER xTX(/xFX)

4. Further support

In the event of technical queries, please talk
to the Hirschmann contract partner respon-
sible for looking after your account or
directly to the Hirschmann office. You can
find the addresses of our contract partners
– on the Internet

(http://www.hirschmann.de).

Our support line is also at your disposal:
Tel. +49(1805) 14-1538
Fax +49(7127) 14-1551

Answers to Frequently Asked Questions can
be found on the Hirschmann internet site 
www.hirschmann.de
The FAQs are located under „Service“ in
the Automation and Network Solutions
section.
www.hicomcenter.com gives you an up-to-
date overview of training courses about
technology and products.

Summary of Contents for SPIDER 4TX/1FX

Page 1: ...nts to the TP ports using twisted pair cabling The SPIDER 8TX devices have eight 10 100 MBit s twisted pair ports RJ45 connectors It is possible to connect up to eight data terminal equipments or other network segments to the TP ports using twisted pair cabling The SPIDER 4TX 1FX devices have four 10 100 MBit s twisted pair ports RJ45 connectors and one 100 MBit s fiber optic port 100BASE FX Duple...

Page 2: ... in the catalog and technical description and only in conjunction with external devices and components recommen ded or approved by Hirschmann The product can only be operated correctly and safely if it is transpor ted stored installed and assembled properly and correctly Furthermore it must be operated and serviced carefully Safety Guidelines Power Supply Switch the basic devices on only when the ...

Page 3: ...d devices or systems in accordance with current safety enginee ring standards trained or directed in the care and use of appropriate safety equipment in accor dance with the current standards of safety engineering trained in providing first aid General Safety Instructions This device is electrically operated Adhere strictly to the safety requirements relating to voltages applied to the device as d...

Page 4: ...oes not transmit any data to a TP segment from which it does not receive a link test pulse Note A non occupied interface is assessed as a line interrupt The TP line to terminal equipment which is switched off is likewise assessed as a line interrupt as the de energised bus coupler cannot transmit link test pulses Auto polarity exchange If the receive line pair is incorrectly connec ted RD and RD s...

Page 5: ...der the low light level If Far End Fault is re ceived the link stays inactive DA STAT LED dark 1 4 FURTHER FUNCTIONS AND FEATURES Reset The SPIDER xTX xFX will be reset by the following action input voltages fall below a threshold After a reset the following action is carried through initialization 1 5 DISPLAY ELEMENTS Equipment status These LEDs provide information about statuses which affect the...

Page 6: ...tact discharge EN 61000 4 2 Test level 3 Air discharge EN 61000 4 2 Test level 3 Electromagnetic fields EN 61000 4 3 Test level 3 Fast transients EN 61000 4 4 Test level 3 Surge voltage symmetrical EN 61000 4 5 Test level 2 Surge voltage asymmetrical EN 61000 4 5 Test level 3 Cable based RF faults EN 61000 4 6 Test level 3 Fig 5 Assembling the SPIDER xTX xFX Fig 6 Dimensions 13 7 70 63 3 23 8 5 3 ...

Page 7: ... 100 MBit s 1 FX Port Duplex SC connection 100 MBit s SPIDER 5TX 5 TP TX Ports RJ45 sockets 10 100 MBit s SPIDER 8TX 8 TP TX Ports RJ45 sockets 10 100 MBit s Displays Equipment status 1 x green LED P power supply voltage present Port status SPIDER 4TX 1FX 5 x green LEDs DA STAT data link status 4 x yellow LEDs 10 100 data rate SPIDER 5TX 5 x green LEDs DA STAT data link status 5 x yellow LEDs 10 1...