5. Technical data
General data
Operating voltage
NEC Class 2 power source 9.6 VDC … 32.0 VDC safety extra-low voltage (SELV/PELV)
5 A maximum
Buffer time
min. 10 ms at 20.4 VDC
Potential difference between input
Potential difference to input voltage, +24 VDC: 32 VDC
voltage and housing
Potential difference to input voltage, ground: -32 VDC
Current consumption at 24 VDC
2.2 W maximum; 7.5 Btu (IT)/h
SPIDER 5TX
3.9 W maximum; 13.3 Btu (IT)/h
SPIDER 8TX
3.9 W maximum; 13.3 Btu (IT)/h
SPIDER 4TX/1FX
Dimensions W x H x D
25 mm x 114 mm x 79 mm
1.0 in x 4.5 in x 3.2 in
SPIDER 5TX
40 mm x 114 mm x 79 mm
1.6 in x 4.5 in x 3.2 in
SPIDER 8TX
25 mm x 114 mm x 79 mm
1.0 in x 4.5 in x 3.2 in
SPIDER 4TX/1FX
Weight
113 g
0.25 lb
SPIDER 5TX
177 g
0.39 lb
SPIDER 8TX
120 g
0.27 lb
SPIDER 4TX/1FX
Ambient temperature
Surrounding air 0 ºC to + 60 ºC
32 ºF to 140 ºF
Storage temperature
Surrounding air - 40 ºC to + 70 ºC
-40 ºF to 158 ºF
Humidity
up to 95% (non condensing)
Atmospheric pressure
up to 2000 m (795 hPa, higher altitudes on demand)
Pollution Degree
2
Protection type
IP 30
Interference proof
Discharge of static electricity
Contact discharge
EN 61000-4-2 Test level 3
Air discharge
EN 61000-4-2 Test level 3
Electromagnetic fields
EN 61000-4-3 Test level 3
Fast transients
EN 61000-4-4 Test level 3
Surge voltage symmetrical
EN 61000-4-5 Test level 2
Surge voltage asymmetrical
EN 61000-4-5 Test level 3
Cable-based RF faults
EN 61000-4-6 Test level 3
Fig. 5: Assembling the SPIDER xTX(/xFX)
Fig. 6: Dimensions
13,7
70
63,3
23
8,5
3.3 STARTUP PROCEDURE
You start up the SPIDER xTX(/xFX) by
connecting the supply voltage via the 3-pin
terminal block.
3.4 DISMANTLING
To take the SPIDER xTX(/xFX) off the
ISO/DIN rail, unlock the snap-in mechanism
according to Fig 7.
Fig. 7: Dismantling the SPIDER xTX(/xFX)
4. Further support
In the event of technical queries, please talk
to the Hirschmann contract partner respon-
sible for looking after your account or
directly to the Hirschmann office. You can
find the addresses of our contract partners
– on the Internet
(http://www.hirschmann.de).
Our support line is also at your disposal:
Tel. +49(1805) 14-1538
Fax +49(7127) 14-1551
Answers to Frequently Asked Questions can
be found on the Hirschmann internet site
www.hirschmann.de
The FAQs are located under „Service“ in
the Automation and Network Solutions
section.
www.hicomcenter.com gives you an up-to-
date overview of training courses about
technology and products.