value)Hz/S. The indoor and outdoor fans run.
Conditions for ending over-current
frequency decreasing
: when the current drops below “current value
for starting the refrigeration current protective prohibition of frequency rising (E2 value)”, over-current
under-clocking will be released.
3.Prohibition of frequency increasing of compressor exhausting
Conditions for prohibition of frequency rising of compressor discharge
Condition 1: in the case of frequency decreasing of compressor discharge, the discharge temperature of
the compressor drops below X4
℃
.
Condition 2: in normal operation, the discharge temperature of compressor reaches X5
℃
.
Either of the above two conditions is met, prohibition of frequency rising of compressor discharge begins.
Actions relates to prohibition of frequency rising of compressor discharge: the frequency of compressor
maintains at the current level, which may decrease as the case requires while cannot rise. The indoor and
outdoor fans run.
Condition for ending prohibition of frequency rising of compressor discharge: if the temperature of
compressor discharge drops below X6
℃
, prohibition of frequency rising of compressor discharge will be
released.
4. Prohibition of frequency for anti-overload of outdoor coiled pipe
Condition for anti-overload prohibition of frequency of outdoor coiled pipe: in the case of anti-overload
frequency decreasing of outdoor coiled pipe, anti-overload prohibition of frequency of the unit begins
when the temperature of outdoor coiled pipe drops below “the anti-overload frequency decreasing
temperature of outdoor coiled pipe”.
Actions relates to anti-overload prohibition of frequency of outdoor coiled pipe: the frequency of
compressor maintains at the current level, which may decrease as the case requires while cannot rise.
The indoor and outdoor fans run.
Condition for ending anti-overload prohibition of frequency of outdoor coiled pipe: if the temperature of
outdoor coiled pipe drops below “temperature to release the anti-overload state of outdoor coiled pipe”,
anti-overload prohibition of frequency of outdoor coiled pipe will be released.
7-4. Trouble Diagnosis of Compressor
Judging the connecting terminals of inverter compressor:
It is impossible to identify terminals U, V and W of inverter compressor with multi-meter. Just connect
the terminals in the same way as the original unit when replacing the compressor. A wrong connection will
lead to reverse and loud noise of the compressor.
Resistance of compressor coil:
Measure the resistance between any two terminals, which are about a few Ohms, three phases
having the same resistance.
76
Summary of Contents for AS-09TR2SYDDC01
Page 13: ...View Model R2 View 3 2 Product dimensions Indoor units 13...
Page 19: ...1802900 1902289 19...
Page 20: ...1854605 1861005 20...
Page 21: ...1867560 1875124 21...
Page 22: ...1874568 1847397 22...
Page 23: ...1852066 Outdoor 1507746 23...
Page 24: ...1826526 1854707 24...
Page 25: ...1877957 1852132 25...
Page 26: ...1854446 4 3 Refrigerant Flow System 26...
Page 31: ...J1 06 31...
Page 32: ...R1 01 32...
Page 33: ...33...
Page 34: ...R2 01 Function Instruction 34...
Page 45: ...1916682 45...
Page 47: ...Model of outdoor 1555069 1887379 47...
Page 48: ...1841765 48...
Page 50: ...1952498 50...
Page 78: ...2 DC Fan test point 78...
Page 79: ...3 4 79...
Page 80: ...5 80...
Page 81: ...81...
Page 82: ...DC fan motor test point 82...
Page 83: ...AC voltage test point Sensor test point 6 83...
Page 84: ...test point Check the screw of IPM fastening test point Forward of IPM P U P V P W test 84...
Page 86: ...test point The resistance of the compressor U W V W 7 SI and N test point 86...
Page 87: ...87...