24
position plus 5º.
4-3-8-4 Outdoor fan
The outdoor fan speeds except single speed motor can be changed according to outdoor ambient
temperatures.
3-7-6 4-way valve
State: It is electrified in heating.
Switchover: When initially powered on for heating, the 4-way valve is activated immediately.
In the change from cooling to heating, it needs an interval of 50 seconds for the 4-way valve to
change over from being interrupted to being activated.
3-8 The super function (option)
In cooling mode, when you press the SUPER button by remote control, the unit will operate for 15
minutes with the following setting:
a.
The set temperature is 16
℃
;
b.
The fan speed with highest speed;
c.
The compressor runs with high frequency.
3-9 Dehumidifying mode
The dehumidifying mode is illustrated as follows:
Dehumidifying area I: Operation at the frequency in the range (30–60Hz) according to Dt (T
indoor
ambient
-T
set
).
Dt(
℃
)
f(Hz)
0
30
Summary of Contents for AS-36HR4SDKVT
Page 1: ...1 Version 1 5 Hisense Corporation MODEL AS 36HR4SDKVT STRONG NEO Premium Classic A...
Page 7: ...7 3 2 Product dimensions Indoor units Model W mm H mm D mm AS 36HR4SDKVT 1280 345 250...
Page 13: ...13 1837708 Outdoor 1821214 Indoor...
Page 18: ...18...
Page 27: ...27 IU PCB 1 IU PCB 5...
Page 28: ...28 OU PCB 1...