(B) DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES). It will cause a serious accident.
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked in the table are selected at the maximum current of the unit
according to the European Standard, EN60335-1. Use the wires which are not lighter than the ordinary
tough rubber sheathed flexible cord (code designation H07RN-F) or ordinary polychloroprene sheathed
flexible cord (code designation H07RN-F).
3) Use a shielded cable for the transmitting circuit and connect it to the ground.
4)
In the case that power cables are connected in series, add each unit maximum current and select
wires below.
* In the case that current exceeds 63A, do not connect cables in series.
Current i(A)
Wire Size(mm
2
)
i
≤
6
0
.
75
6
<
i
≤
10
1
10
<
i
≤
16
1
.
5
16
<
i
≤
25
2
.
5
25
<
i
≤
32
4
32
<
i
≤
40
6
40
<
i
≤
63
10
63
<
i
*
Selection According to EN60335-1