Running Parameter Query
Running parameter can be referred by digital tube switch or specified wired remote controller.
Query by
wire
d
remote controller (YXE-C01U,YXE-C02U,YXE-D01U)
Operation:
1.Connect
the
wire
d
remote controller with
the
indoor unit
(same method as Indoor unit parameter revis
ion
)
2.Chang
e
the
system parameter
OPERATION
:
①
Hold down both“MODE”button and“ADD.FUNC.”button for 3 seconds, symbol
and parameter
number blink at the same time.
②
Press“ ”“
”button to select parameter number as you need, parameter value will be displayed on
the LCD.
Parameter Code
Parameter Description
06
Indoor unit air inlet temperature
07
Indoor unit coil sensor temperature
08
Outdoor unit ambient sensor temperature
09
Discharge temperature
10
Suction temperature
11
Outdoor coil temperature
12
Discharge pressure
13
Suction pressure
14
Outdoor EEV opening
15
AC current input
16
AC voltage
24
Fault code
25
Drive fault code
26
Indoor unit air outlet temperature
28
Compressor current
29
Indoor unit room temperature
30
Indoor unit coil inlet temperature
31
Indoor unit coil outlet temperature
32
Outdoor unit condenser inlet temperature
33
Outdoor unit condenser outlet temperature
43
Outdoor unit defrost temperature
57
Outdoor fan 1 speed
58
Outdoor fan 2 speed
60
Indoor fan speed
NOTE: For some models, some parameter values will not display on the wired controller.