Function Setting
No.
Setting Item
7-Segment
Display
Contents
SEG2 SEG1
1
Circular at Heating Function
Thermo-off
FA
00
No setting
01
Indoor fan forced ON and OFF (2 min. ON / 6 min. OFF)
2
Night-Shift
ni
00
No Setting
01
Setting of night-shift
3
Cancellation of Outdoor Ambient
Temperature Limit
GS
00
No setting
01
For heating
02
For cooling
03
For cooling/heating
4
Defrost for Cold Area
(Change of Defrost Condition)
Jo
00
No setting
01
Condition 2 of defrost operation
5
SLo (Fan Speed)
Defrost Setting
bJ
00
Indoor fan stop when heating operation is activated/during defrost operation
01
Indoor fan SLo operation during defrost operation
02
Indoor fan SLo operation when heating operation is activated
03
Fan operation when heating operation is activated/
Indoor fan SLo operation during defrost operation
6
Cancellation of Hot Start
HT
00
Hot start control is available
01
Cancellation of hot start
7
Priority Capacity Mode
nU
00
No setting
01
Change of frequency maximum limit value
02
Change of current limit value
03
Change of frequency maximum limit value and current limit value
8
Compressor Frequency Control
Target Value for Cooling
Hc
00
Initial setting (Ps evaporation temperature targeted value 7
o
C)
01
Targeted value (2
o
C)
02
Targeted value (3
o
C)
03
Targeted value (4
o
C)
04
Targeted value (5
o
C)
05
Targeted value (9
o
C)
06
Targeted value (10
o
C)
07
Targeted value (11
o
C)
08•09
Not prepared (If set, the setting item will be ignored by the control PCB.)
9
Compressor Frequency Control
Target Value for Heating
Hh
00
Initial setting (Ps targeted value 2.85MPa)
01
Targeted value (2.60MPa)
02
Targeted value (2.75MPa)
03
Targeted value (2.80MPa)
04
Targeted value (2.82MPa)
05
Targeted value (2.88MPa)
06
Targeted value (2.90MPa)
07
Targeted value (2.95MPa)
08•09
Not prepared (If set, the setting item will be ignored by the control PCB.)
10
Indoor Expansion Valve Control
Target Value for Cooling
SC
00
Initial setting (SH targeted value +5
o
C)
01
SH Targeted value 7
02
SH Targeted value 6
03
SH Targeted value 4
04
SH Targeted value 3
05~09 Not prepared (If set, the setting item will be ignored by the control PCB.)
11
Indoor Expansion Valve Control
Target Value for Heating
SH
00
Initial setting (SC targeted value +5
o
C)
01
SC Targeted value 11
02
SC Targeted value 8
03
SC Targeted value 2
04
SC Targeted value -1
05~09 Not prepared (If set, the setting item will be ignored by the control PCB.)
12
Indoor Expansion Valve
Opening Change for
Stoppage Indoor Unit
in Heating Mode
Si
00
Initial setting (stoppage unit expansion valve opening (150~325 pulse))
01
Expansion valve opening 07~22: 175 pulse, 24 or over: 300 pulse
02
Expansion valve opening 07~22: 100 pulse, 24 or over: 150 pulse
03~09 Not prepared (If set, the setting item will be ignored by the control PCB.)
13
Indoor Expansion Valve
Opening Change for
Thermo-OFF Indoor Unit
in Heating Mode
So
00
Thermo-OFF unit expansion valve opening (150~325 pulse)
01
Expansion valve opening 07~22: 175 pulse, 24 or over: 300 pulse
02
Expansion valve opening 07~22: 100 pulse, 24 or over: 150 pulse
03~09 Not prepared (If set, the setting item will be ignored by the control PCB.)
167