15.4.2 Troubleshooting Procedure
ϥ
Alarm Code Indication of Remote Control Switch
●
Alarm Code Table
Code
Category
Content of Abnormality
Leading Cause
01
Indoor Unit
Activation of Protection Device (Float Switch)
Activation of Float Switch
(High Water Level in Drain Pan,
Abnormality of Drain Pipe, Float Switch or Drain Pan)
02
Outdoor Unit Activation of Protection Device
(High Pressure Cut)
Activation of PSH (Pipe Clogging, Excessive
Refrigerant, Inert Gas Mixing)
03
Transmission
Abnormality between Indoor and Outdoor
Incorrect Wiring, Loose Terminals, Disconnect Wire,
Blowout of Fuse, Outdoor Unit Power OFF
04
04.
Abnormality between Inverter PCB and Outdoor PCB
Abnormality between Fan Controller and Outdoor PCB
Inverter PCB - Outdoor PCB Transmission Failure
(Loose Connector, Wire Breaking, Blowout of Fuse)
(Loose Connector, Wire Breaking, Blowout of Fuse)
Fan Controller - Outdoor PCB Transmission Failure
05
Supply Phase Abnormality Power Source Phases
Incorrect Power Source, Connection to
Reversed Phase, Open-Phase
06
Voltage
Abnormal Inverter Voltage
Outdoor Voltage Drop, Insufficient Power Capacit
06.
Abnormal Fan Controller Voltage
Outdoor Voltage Drop, Insufficient Power Capacit
07
Cycle
Decrease in Discharge Gas Superheat
Excessive Refrigerant Charge, Failure of Thermistor,
Incorrect Wiring, Incorrect Piping Connection,
Expansion Valve Locking at Opened Position
(Disconnect Connector)
08
Increase in Discharge Gas Temperature
Insufficient Refrigerant Charge, Pipe Clogging
Failure of Thermistor, Incorrect Wiring,
Incorrect Piping Connection, Expansion Valve Locking
at Closed Position (Disconnect Connector)
0A
Transmission Abnormality between Outdoor and Outdoor
Incorrect Wiring, Breaking Wire, Loose Terminals
0b
Outdoor Unit
Incorrect Outdoor Unit Address Setting
Duplication of Address Setting for Outdoor Units
(Sub Units) in Same Refrigerant Cycle System
0C
Incorrect Outdoor Unit Main Unit Setting
Two (or more) Outdoor Units Set as “Main Unit”
Exist in Same Refrigerant Cycle System
11
Sensor on
Indoor Unit
Inlet Air Thermistor
Incorrect Wiring, Disconnecting Wiring
Breaking Wire, Short Circuit
Incorrect Wiring, Disconnecting Wiring
Breaking Wire, Short Circuit
12
Outlet Air Thermistor
13
Freeze Protection Thermistor
14
Gas Piping Thermistor
19
Fan Motor
Activation of Protection Device for Indoor Fan
Fan Motor Overheat, Locking
21
Sensor on
Outdoor Unit
High Pressure Sensor
22
Outdoor Air Thermistor
23
Discharge Gas Thermistor on Top of Compressor
24
Heat Exchanger Liquid Pipe Thermistor
25
Heat Exchanger Gas Pipe Thermistor
29
Low Pressure Sensor
Alarm Code
186