(D) Indoor Unit Information
2
4
3
6
5
Details of Indication
7
Unit:
o
C
Unit:
o
C
Unit:
o
C
Unit No.
No.0
No.1
No.63
Indication
Item
Indoor Unit Capacity
Expansion Valve Opening
Heat Exchanger Liquid Piping Temp.
Heat Exchanger Gas Piping Temp.
Air Inlet Temp.
Air Outlet Temp.
Unit Stoppage Cause Code
Unit:
o
C
Indoor Unit Stoppage Cause Code Indication
Refer to “Cause of Indoor Unit Stoppage Table”.
Unit Capacity Indication
Refer to “Indoor Unit Capacity Table”.
Unit: %
Degeneracy Control for
Pressure Ratio Decrease Protection
Degeneracy Control for
High Pressure Increase Protection
Degeneracy Control for
Inverter Fin Temp. Increase Protection
Degeneracy Control for
Discharge Gas Temp. Increase Protection
Degeneracy Control for
Td SH Decrease Protection
Degeneracy Control for
Overcurrent Protection
Latest O.U. Stoppage Alarm Code Indication
Refer to “Alarm Code Table”.
Alarm Cause Code
This information is indicated on the unit A (main unit) only.
Select the indoor unit number for the information indication.
Press PSW4 ( ) to forward or press PSW2 ( ) for backward.
Select the indoor unit No. for indication.
Press PSW3 ( ) for details information of selected unit No..
Press PSW4 ( ) to forward or PSW2 ( ) to backward.
The information will be indicated alternately as “Item” “Details”
Press PSW5 ( ) for return to Indoor Unit No. Selection.
(E) Cause of Alarm Code Information
2
4
3
6
5
Details of Indication
7
This information is indicated on the unit A (main unit) only.
Press PSW4 ( ) to forward or press PSW2 ( ) to backward.
The indication will be indicated alternately as “Item” “Details”.
NOTE: The indoor unit No. is indicated on “SEG1” .
SEG2 SEG1
: Degeneracy Control is not Activated.
: Degeneracy Control is Activated.
: Degeneracy Control is not Activated.
: Degeneracy Control is Activated.
: Degeneracy Control is not Activated.
: Degeneracy Control is Activated.
: Degeneracy Control is not Activated.
: Degeneracy Control is Activated.
: Degeneracy Control is not Activated.
: Degeneracy Control is Activated.
: Degeneracy Control is not Activated.
: Degeneracy Control is Activated.
(Example)
kBtu/h
kBtu/h
kBtu/h
Indoor Unit Capacity Table
Indication
Capacity
(kW)
6
2.2
7
8
2.8
9
10
3.6
12
11
4.0
13
13
4.5
14
14
5.0
17
Indication
Capacity
(kW)
16
5.6
18
18
6.3
22
20
7.1
24
22
8.0
27
26
9.0
30
32
11.2
38
Indication
Capacity
(kW)
40
14.0
48
48
16.0
54
64
22.4
76
80
28.0
96
128
45.0
154
160
56.0
190
1
1
Details
SEG1
SEG2
7-Segment Display
Item
Details
SEG1
SEG2
7-Segment Display