A
VWT-76*~
454
*
t
One 90° Elbow is 0.5m.
t
One 180° Bend is 1.5m.
t
One Branch Pipe is 0.5m.
4.5 Capacity Correction Based On Refrigerant Piping Length
< Cooling Capacity >
Correction Factor for Cooling Capacity According to Piping Length
The cooling capacity should be corrected according to the following formula:
CCA=CC×F
CCA: Actual Corrected Cooling Capacity
CC: Cooling Capacity in the Performance Table
F: Correction Factor Based on the Equivalent Piping Length
The correction factors are shown in the following figure
Equivalent Piping Length for
Normal
Size up