18
Water Flow Rate and Pressure Drop
Select the water pump (field-supplied) according to the following table
Relation of water flow rate and pressure drop of each water source unit model is shown in the chart below.
In case the water source unit operate above the rated water flow rate, the water pump power consumption is
increased. It is recommended to operate below the rated water flow rate
6.2 Water Flow Rate and Pressure Drop
Model
76
96
114
136
154
170
190
Rated Water Flow Rate
[m
3
/h]
4.60
5.76
6.90
8.30
9.20
10.00
11.60
Allowable Water
Flow Rate
[m
3
/h]
Maximum
3.04
3.80
4.55
5.48
6.07
6.60
7.66
Minimum
2.53
3.15
3.80
4.57
5.06
5.50
6.38
Pressure Drop
kpa
Flow Rate
m
3
/h
76/96
114/136
154/170/190
Summary of Contents for AVWW-114FKFW