4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
97
4
4.8
Troubleshooting by alarm code
Alarm code
C1-H1
High Pressure Switch
Alarm stop reason
Discharge pressure (Pd) increases up to 2.02MPa, activating high pressure switch (63H).
PCB monitoring position
PCBd (I/O PCB) PCN204 (High pressure interruption device (63H))
Check of PCBd (I/O PCB)
Press the reset button of
high pressure switch
Check of high pressure
switch (63H) (Internal
disconnection)
Check of wiring
(disconnection)
Excessive refrigerant load
In case of cooling operation
I/O PCB is normal
Check of PCBd (I/O PCB)
Yes
No
Yes
No
Revision of connections
The connection and
insertion of connector
PCN204 to PCBd (I/O
PCB) are correct
Yes
No
Yes
No
Yes
No
Remove the wires
inserted in PCN204
on PCBd (I/O PCB) and
check power conduction.
Is there power
conduction?
High pressure
switch (63H) is
activated.
Operation control results
in immediate alarm
High pressure
switch (63H) is being
reset