4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
104
Alarm code
C1-t1
Suction gas decrease
Alarm stop reason
Temperature of refrigerant suctioned into compressor (Ts) falls below -5ºC for more than 10 seconds.
N O T E
Causes alarm stop with 3 occurrences in 30 minutes. Retry control is performed until the second one. (Compressor
stops, and restarts automatically after 3 minutes)
Retry indication
LCD: By touching “Inspection”, “Ts Retry” is shown in “No.1 Cycle”.
Retry code
C1-P6
PCB monitoring position
PCBd (I/O PCB) CN27 (Suction gas thermistor)
Clogging of water strainer
Adjustment of cold water thermo settings.
Shall be within usage range
Adjustment of air mixture
Adjustment of reverse rotation of pump
Adjustment of water quantity (adjustment
of inlet-outlet water temperature)
Replace thermistor
Correction of
connections
Check of PCB
d
(I/O PCB)
The connection and
insertion of connector
CN27 on PCB
d
(I/O PCB)
are correct
Yes
Yes (There are problems)
No (There are no problems)
There are
problems with thermistor
characteristics
Yes
No
No
Compressor
suction gas refrigerant
temperature has actually
dropped to activation
value