4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
110
Alarm code
C1-27
Discharge Pressure Sensor Abnormality (CN31)
Alarm stop reason
Discharge pressure sensor (Pd) of compressor indicates an abnormal value.
PCB monitoring point
PCBd (I/O PCB) CN31PD (Discharge pressure sensor (Pd))
N O T E
Refer pressure sensor characteristics chapter.
Revision of connections
Replace PCBd (I/O PCB)
Replace PCBd (I/O PCB)
Elimination of the factors
for clogging inside the
pipe
Replacement of discharge pressure
sensor
Yes
Yes
Yes
Yes
No
No
No
No
The connection and insertion of connector
CN31Pd on PCBd (I/O PCB) are correct
DC5V is being supplied between pin 1 and pin
3 of connector CN31Pd on PCBd (I/O PCB)
There is clogging inside the connection pipe of
discharge pressure sensor
Is the voltage between pin 2 and pin 3
of connector CN31Pd on PCBd (I/O PCB)
lower than DC0.5V or higher than DC4.5V when
discharge pressure sensor is connected?