2. Control Functions
Control functions on the module
SMGB0097 rev.0 - 07/2015
9
2
2.1.1 Water control
Outlet water temperature of Chiller Unit is detected by Thermistor, and based on this value, compressor ON/OFF and the
most suitable capacity is determined. Following shown the continuous capacity control and change of water temperature.
9ºC
8ºC
7ºC
6ºC
5ºC
(0.5~5.0ºC)
(0.5~2.0ºC)
(1.0~3.0ºC)
T4
Δ
Tsc : 7ºC
T1: 1ºC
T2: 2ºC
T3: 2ºC
T4: 1ºC
Δ
Δ
Δ
Δ
Tsc (setting t.)
T1
Δ
T2
Δ
T3
Δ
Tsc+ T2/3+ T4
Δ
Δ
Tsc+ T2/3
Δ
Tsc- T2/3
Δ
Tsc- T2/3- T1
Δ
Δ
T3
Δ
T4
Δ
T1
Δ
(1.0~4.0ºC)
T2
Δ
Outlet
temperature
Inlet
temperature
Stop
(Thermo off)
Start
(re-start)
Memorizes the inlet temperature
at Thermo-OFF and re-start at
∆T2
Load up I zone
Load up II zone
Load Down zone
Thermo-off zone
Load up I
status
Load up II
status
Neutral status
Load-down status
Stop
status
Load up II
status
Neutral
status
Neutral status
Neutral zone
Starting setting
(example)
Method of outlet temperature detection
1
Load-up I control at over 9°C (The capacity is changed a lot in order to approximate the target temp. quickly)
2
Load-up II control at 8~9°C (The capacity is changed moderately)
3
In neutral zone (6~8°C), load is balanced and performance is not changed.
4
Under neutral zone (below 6°C) load-down control is performed and performance is decreased.
5
Stop temp: Compressor is stopped at 5°C. The inlet temp of that time is saved.
6
When inlet temp becomes 2°C higher than that of at stop, re-start signal is output and unit is re-started after at least 3
min guard.