2. Control Functions
Run operation
SMGB0097 rev.0 - 07/2015
51
2
2.4.2 Operation control of the module
1
In the case of remote control
Operation order
Stop order
Confirm that the cold water inlet/outlet valve is fully open
Power ON
Press the “Run” button
Press the “Stop” button
Operation of pump for cold water circulation starts
Operation of compressor starts after compressor delay time has passed
Power ON the pump for cold water circulation
N O T E
It is possible to stop the module by means of the stop switch in the Master module, even if it is in remote operation. It is
also possible to stop by rem
ote controller switch even during local operation.
2
In the case of local control
It is possible to control this product remotely. Follow the procedure below in case that it is absolutely necessary to control
it from the Master module, such as during test run or in servicing.
Operation order
Stop order
Press the “Stop” button
Close the door inside the electrical parts box
Close the door inside the electrical parts box
Close the door inside the electrical
parts box, then close the door of the
electrical parts box
Open the door inside the electrical parts box
Preparations for remote control complete
Open the door of the
electrical parts box and
control the microprocessor
Open the door of he electrical
parts box, and the door inside the
electrical parts box, and control
the microprocessor.
Confirm that the module is being powered ON
Confirm that the pump for cold water circulation is being
powered ON
Set the “local/remote switch” on the setting PCB to “local”
Press the “Run” button
Operation of pump for cold water circulation starts
Operation of compressor starts after compressor delay time has passed
The compressor stops
Set the “local/remote switch” on the setting PCB to
“remote”
Confirm that the cold water inlet/outlet valve is fully open