3. Servicing
Cycle components
SMGB0097 rev.0 - 07/2015
68
3.3.3
Recovering the refrigerant
With a vacuum pump
a.
Make sure that the system is powered off.
b.
Completely close the stop valve.
c.
Connect the vacuum pump system to the check joints of the refrigerant line.
d.
Check for any leakage at the flare nuts connections.
e.
Operate the vacuum pump for 1 or 2 hours, or until the pressure decreases lower than a pressure of 756 mmHg in
vacuum.
f.
Use a scale to take note of the quantity of refrigerant charged into the tank in order to provide the same quantity
when charging the circuit.
Recovery tank
Vacuum pump
Manifold gauge
RCME-CLH unit
Scale
3.3.4
Replacement of the cooler
1
Unscrew the 4 screw of the refrigerant inlet pipe
flange and the 4 screws of the outlet refrigerant
pipe flange.
Bolt
Spring washer
Flange plate
Nut
Spring washer
Gasket
Flat washer
Cooler
Outlet pipe flange
4 Screws
Inlet pipe flange 4
Screws