3. Servicing
Cycle components
SMGB0097 rev.0 - 07/2015
76
3.3.19
Replacement of the thermistor (Evaporation, THMe)
1
Cut and remove the plastic bands that fixes
the insulation of the discharge pipe thermistor
(THMe).
2
Loosen the screw fixing the thermistor.
3
At the E-box, disconnect the CN26TD contact
(or the Faston terminals 9 and 10 of multiple
contact QCN3)
4
Remove the thermistor.
5
When reassembling after replacing the thermis
-
tor (THMe, perform the procedure in the reverse
order than removing.
Thermistor THMe
Evaporation pipe
Thermistor THMe
Screw
Plastic bands
3.3.20
Replacement of the thermistor (Cooler water inlet, THMwi)
1
Unscrew the nut of the cable gland
2
Gently pull the sensor wiring upwards.
C A U T I O N
Sensor sheath is full of sealing silicone. Use gloves
and eye goggles for protection in order to avoid
possible injuries to eyes and skin.
3
Disconnect the 3 and 1 Faston terminals or the
CN5 connector at the E-box
4
Replace the thermistor in reverse order than re
-
moving.
N O T E
Use sealant silicone inside the sensor sheath to
protect and avoid any leakage.
Thermistor (THMwi
Cable gland
Fitting adaptor
Sensor sheath
Sensor
Sensor wiring