Table 13: Description of the columns in the export file
Column
Description
CAA
Common Address ASDU: Sub-address for identifying a Bay Unit
at the application level
ABB ref.:
ABB’s designation for the Bay Unit
Feeder:
User’s designation for the respective bay
Station Number:
Disturbance recorder number
Signal ID:
Consecutive signal number
Signal Text:
User’s signal description
IEC FUN:
Assigned IEC function type
IEC INF:
Assigned IEC information number
The above Signal ID and Signal Text assignment for a specific Bay Unit can also be made via
HMI500 providing a COMTRADE file for the Bay Unit disturbance recorder is uploaded. The file
filename.cfg generated by the PC contains the same information as the list generated by the
export tool.
The assignment can change when the disturbance recorder configuration changes, for
example, by deleting or adding signals. The above list then has to be recreated and possibly
corrected by the control system.
The configured length of disturbance records shall not exceed one second (1 s)
to avoid conflicts with the maximum number of 65535 events foreseen in IEC
60870-5-103.
4.4
ACC actual channel
GUID-1AC25D43-EFDB-4521-9ACB-FE818FB9CAF8 v2
The REB500 Bay Unit 500BU04 supports five voltage channels. Since, however, the compatible
range of the standard only lists four voltage channels, the fifth channel is transferred to the
private domain.
Assignment of REB500 channels to IEC 60870-5-103 channel numbers:
Table 14: IEC 60870-5-103 analogue channel assignment
REB500 channel
designation
REB500 application
IEC 60870-5-103 channel designation ACC
(actual channel)
I1
I L1
1 = I L1
I2
I L2
2 = I L2
I3
I L3
3 = I L3
I4
I L0
4 = V L1
U1
U L1
5 = V L1E
U2
U L2
6 = V L3
U3
U L3
7 = V 0E
U4
U L0
8 = U L1
U5
U 5
64 = private
Section 4
1MRK 511 451-UEN Rev. C
IEC 60870-5-103
16
Distributed busbar protection REB500
Communication protocol manual IEC 60870-5-103