8.13.3.4
Space Heating / Space Cooling configuration
Control the temperature for Space Heating or Space Cooling by configuring the following parameters.
Working Limits:
Limit for the temperature set-point to
prevent high or low temperatures at
Space Heating or S
pace Cooling:
•
Maximum supply temperature
•
Minimum supply temperature
Water calculation mode:
Selection of the water set point for
Circuit 1 or Circuit 2 (Space Heating
or Space Cooling).
• Deactivated
•
Points
•
Gradient (only in heating mode)
•
Fix
See detailed explanation below.
Eco Offset Water setting:
Configure the offset water temperature
for the ECO mode for Space Heating
or Space Cooling.
By using this function, current water
temperature setting is reduced by the
indicated parameter.
•
Range: 0 ~ 10
Mixing valve:
To control the second water temperature (only for
circuit 2).
Values are adjusted for the use with the 2nd zone
mixing kit accessory ATW-2KT-05. It is highly
recommended not to change these values.
In case of using a mixing kit different from the
ATW-2KT-05 configure the following parameters:
•
Proportional band: 0~20K (6.0 K by default).
•
Integral reset factor: 0.0~20% (2.5 % by default).
•
Running time factor: 10~250 sec (140 sec by
default).
•
Over temperature offset protection: OFF, 3~10ºC
(5 ºC by default).
YUTAKI CASCADE CONTROLLER
PMML0575 rev.1 - 09/2021
134