3.2 SPLIT SYSTEM - R410A OUTDOOR UNIT
RAS-(4-10)WH(V)NP(E) in combination with YUTAKI S, YUTAKI S COMBI
Model
Power supply
Applicable voltage
Compressor and fan motors
MC
(A)
Max. IPT
(kW)
Cooling
Heating
U max.
(V)
U min.
(V)
RNC
(A)
IPT
(KW)
RNC
(A)
IPT
(KW)
RAS-4WHVNPE
1~ 230V 50Hz
253
207
9.2
2.11
9.3
2.12
30
6.93
RAS-5WHVNPE
12.6
2.87
12.7
2.90
30
6.93
RAS-6WHVNPE
16.0
3.65
15.0
3.43
30
6.93
RAS-4WHNPE
3N~ 400V 50Hz
440
360
3.4
2.11
3.4
2.12
14
8.70
RAS-5WHNPE
4.6
2.87
4.6
2.90
14
8.70
RAS-6WHNPE
5.8
3.65
5.5
3.43
16
9.95
RAS-8WHNPE
7.1
4.41
7.3
4.58
24
15.00
RAS-10WHNPE
9.8
6.15
8.8
5.51
24
15.00
3.3 SPLIT SYSTEM - R32 OUTDOOR UNIT
RAS-(2-3)WHVRP1 in combination with YUTAKI S, YUTAKI S COMBI
Model
Power supply
Applicable voltage
Compressor and fan motors
MC
(A)
Max. IPT
(kW)
Cooling
Heating
U max.
(V)
U min.
(V)
RNC
(A)
IPT
(KW)
RNC
(A)
IPT
(KW)
RAS-2WHVRP1
1~ 230V 50Hz
253
207
4.5
1,00
5.0
1.09
10.4
2.27
RAS-2.5WHVRP1
5.0
1.12
5.5
1.19
12.9
2.82
RAS-3WHVRP1
7.6
1.67
8.1
1.79
15.8
3.49
ELECTRICAL DATA
PMML0575 rev.1 - 09/2021
10