ENGLISH
3.4 SPLIT SYSTEM - INDOOR UNIT
3.4.1 YUTAKI S
RWM-(2.0-10.0)(N/R)1E
Model
Power supply
Applicable voltage
Operation mode
RNC
(A)
IPT
(kW)
MC
(A)
Max.
IPT
(kW)
U max.
(V)
U min.
(V)
RWM-2.0R1E
1~ 230V 50Hz
253
207
Without electric heater
0.5
0.06
0.63
0.06
With electric heater
13.7
3.06
13.7
3.06
With DHW tank heater
13.7
3.06
13.7
3.06
With electric and DHW tank heaters
26.7
6.06
26.7
6.06
3N~ 400V 50Hz
440
360
Without electric heater
0.5
0.06
0.6
0.06
With electric heater
4.8
3.06
5.0
3.06
With DHW tank heater
4.5
3.06
13.7
3.06
With electric and DHW tank heaters
8.9
6.06
18.0
6.06
RWM-(2.5-3.0)R1E
1~ 230V 50Hz
253
207
Without electric heater
0.6
0.06
0.6
0.06
With electric heater
13.7
3.06
13.7
3.06
With DHW tank heater
13.7
3.06
13.7
3.06
With electric and DHW tank heaters
26.7
6.06
26.7
6.06
3N~ 400V 50Hz
440
360
Without electric heater
0.6
0.06
0.6
0.06
With electric heater
4.8
3.06
5.0
3.06
With DHW tank heater
4.5
3.06
13.7
3.06
With electric and DHW tank heaters
8.9
6.06
18.0
6.06
RWM-(4.0-6.0)N1E
1~ 230V 50Hz
253
207
Without electric heater
0.6
0.08
0.7
0.08
With electric heater
26.7
6.08
26.7
6.08
With DHW tank heater
13.7
3.08
13.7
3.08
With electric and DHW tank heaters
39.8
9.08
39.8
9.08
3N~ 400V 50Hz
440
360
Without electric heater
0.6
0.08
0.7
0.08
With DHW tank heater
9.1
6.08
9.3
6.08
With DHW tank heater
4.5
3.08
13.7
3.08
With electric and DHW tank heaters
13.3
9.08
22.4
9.08
RWM-(8.0-10.0)N1E
3N~ 400V 50Hz
440
360
Without electric heater
0.3
0.08
0.7
0.14
With DHW tank heater
13.1
9.08
13.7
9.14
With DHW tank heater
4.5
3.08
13.7
3.14
With electric and DHW tank heaters
17.5
12.08
26.7
12.14
?
N O T E
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL DATA
PMML0575 rev.1 - 09/2021
11