6 ELECTRICAL AND CONTROL SETTINGS
6.1 GENERAL CHECK
•
Make sure that the following conditions related to power supply installation are satisfied:
-
The power capacity of the electrical installation is large enough to support the power demand of the YUTAKI system (outdoor
unit + indoor unit + DHW tank (if apply)).
-
The power supply voltage is within ±10% of the rated voltage.
-
The impedance of the power supply line is low enough to avoid any voltage drop of more than 15% of the rated voltage.
•
Following the Council Directive 2014/30/EU, relating to electromagnetic compatibility, the table below indicates the Maximum
permitted system impedance Z
max
at the interface point of the user’s supply, in accordance with EN61000-3-11.
Split system - R410A Outdoor unit
Model
Power supply
Z
max
(Ω)
RAS-4WHVNPE
1~ 230V 50Hz
0.25
RAS-5WHVNPE
0.25
RAS-6WHVNPE
0.25
RAS-4WHNPE
3N~ 400V 50Hz
-
RAS-5WHNPE
-
RAS-6WHNPE
-
RAS-8WHNPE
-
RAS-10WHNPE
-
Split system - R32 Outdoor unit
Model
Power supply
Z
max
(Ω)
RAS-2WHVRP1
1~ 230V 50Hz
-
RAS-2.5WHVRP1
-
RAS-3WHVRP1
0.43
Split system - Indoor unit
YUTAKI S
Model
Power supply
Operation mode
Z
max
(Ω)
RWM-(2.0-3.0)R1E
1~ 230V 50Hz
Without electric heater
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
0.28
RWM-(2.0-3.0)R1E
3N~ 400V 50Hz
Without electric heater
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
-
RWM-(4.0-6.0)N1E
1~ 230V 50Hz
Without electric heater
-
With electric heater
0.28
With DHW tank heater
-
With electric and DHW tank heaters
0.19
3N~ 400V 50Hz
Without electric heater
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
-
RWM-(8.0/10.0)N1E
3N~ 400V 50Hz
Without electric heater
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
-