N O T E
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
YUTAKI S COMBI
Model
Power supply
Operation mode
Z
max
(Ω)
RWD-(2.0-3.0)RW1E-
220S(-K)
1~ 230V 50Hz
Without electric heaters
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
0.29
RWD-(2.0-3.0)RW1E-
220S(-K)
3N~ 400V 50Hz
Without electric heaters
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
-
RWD-(4.0-6.0)NW1E-
220S(-K)
1~ 230V 50Hz
Without electric heaters
-
With electric heater
0.28
With DHW tank heater
-
With electric and DHW tank heaters
0.19
3N~ 400V 50Hz
Without electric heaters
-
With electric heater
-
With DHW tank heater
-
With electric and DHW tank heaters
-
•
The status of Harmonics for each model, regarding compliance with EN 61000-3-2 and EN 61000-3-12, is as follows:
Status regarding compliance with
EN 61000-3-2 and EN 61000-3-12
Models
Split system
Outdoor unit
Indoor unit
YUTAKI S
YUTAKI S COMBI
Equipment complying with EN 61000-3-2
(*): Professional use
RAS-2WHVRP1(*)
RAS-2.5WHVRP1(*)
RAS-3WHVRP1 (*)
RAS-4WHNPE (*)
RAS-5WHNPE (*)
RAS-6WHNPE (*)
RWM-2.0R1E
RWM-2.5R1E
RWM-3.0R1E
RWM-4.0N1E (3N~)
RWM-5.0N1E (3N~)
RWM-6.0N1E (3N~)
RWM-8.0N1E
RWM-10.0N1E
-
Equipment complying with EN 61000-3-12
RAS-4WHVNPE
RAS-5WHVNPE
RAS-6WHVNPE
RWM-4.0N1E (1~)
RWM-5.0N1E (1~)
RWM-6.0N1E (1~)
RWD-2.0RW1E-220S
RWD-2.5RW1E-220S
RWD-3.0RW1E-220S
RWD-4.0NW1E-220S
RWD-5.0NW1E-220S
RWD-6.0NW1E-220S
Installation restrictions may be applied by supply
authorities in relation to harmonics
RAS-8WHNPE
RAS-10WHNPE
-
-
•
Check to ensure that existing installation (main power switches, circuit breakers, wires, connectors and wire terminals) already
complies with the national and local regulations.
•
The use of the DHW tank heater is disabled as factory setting. If it is desired to enable the DHW tank heater operation during
normal indoor unit operation, adjust the DSW4 pin 3 of the PCB1 to the ON position and use the adequate protections. Refer to
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.1 - 09/2021
30