ENGLISH
YUTAKI S COMBI
Model
Power supply
Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
Actuator
cables
EN60335-1
EN60335-1
EN60335-1
RWD-(2.5-3.0)RW1E-
220S(-K)
1~230V 50Hz
Without electric heaters
0.63
2 x 0.75 mm² + GND
2 x 0.75 mm
2
(Shielded
cable)
2 x 0.75 mm
2
+ GND
With electric heater
13.7
2 x 2.5 mm² + GND
With DHW tank heater
12.6
2 x 2.5 mm² + GND
With electric and DHW tank heaters
25.6
2 x 6.0 mm² + GND
RWD-(2.5-3.0)RW1E-
220S(-K)
3N~400V 50Hz
Without electric heaters
0.63
4 x 0.75 mm² + GND
With electric heater
9.3
4 x 2.5 mm² + GND
With DHW tank heater
12.6
4 x 2.5 mm² + GND
With electric and DHW tank heaters
12.6
4 x 2.5 mm² + GND
RWD-(4.0-6.0)NW1E-
220S(-K)
1~230V 50Hz
Without electric heaters
0.65
2 x 0.75 mm² + GND
With electric heater
26.7
2 x 6.0 mm² + GND
With DHW tank heater
12.6
2 x 2.5 mm² + GND
With electric and DHW tank heaters
38.7
2 x 10.0 mm² + GND
3N~400V 50Hz
Without electric heaters
0.65
4 x 0.75 mm² + GND
With electric heater
18.0
4 x 6.0 mm² + GND
With DHW tank heater
12.6
4 x 2.5 mm² + GND
With electric and DHW tank heaters
18.0
4 x 6.0 mm² + GND
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.1 - 09/2021
33