6.2 ELECTRICAL CONNECTION
!
C A U T I O N
•
Check to ensure that the field supplied electrical components (mains power switches, circuit breakers, wires, connectors and wire terminals) have
been properly selected according to the electrical data indicated on this chapter and they comply with national and local codes. If it is necessary,
contact with your local authority in regards to standards, rules, regulations, etc.
• Use a dedicated power circuit for the indoor unit. Do not use a power circuit shared with the outdoor unit or any other appliance.
6.2.1 Wiring size
Use wires which are not lighter than the polychloroprene sheathed flexible cord (code designation 60245 IEC 57).
Split system - R410A Outdoor unit
Model
Power supply
Max. current (A)
Power supply cables
Transmitting cables
Actuator cables
EN60335-1
EN60335-1
EN60335-1
RAS-4WHVNPE
1~ 230V 50Hz
30
2 x 6.0 mm
2
+ GND
2 x 0.75 mm
2
(Shielded cable)
2 x 0.75 mm
2
+ GND
RAS-5WHVNPE
30
2 x 6.0 mm
2
+ GND
RAS-6WHVNPE
30
2 x 6.0 mm
2
+ GND
RAS-4WHNPE
3N~ 400V 50Hz
14
4 x 2.5 mm
2
+ GND
RAS-5WHNPE
14
4 x 2.5 mm
2
+ GND
RAS-6WHNPE
16
4 x 4.0 mm
2
+ GND
RAS-8WHNPE
24
4 x 6.0 mm
2
+ GND
RAS-10WHNPE
24
4 x 6.0 mm
2
+ GND
Split system - R32 Outdoor unit
Model
Power supply
Max. current (A)
Power supply cables
Transmitting cables
Actuator cables
EN60335-1
EN60335-1
EN60335-1
RAS-2WHVRP1
1~ 230V 50Hz
10.4
2 x 2.5 mm² + GND
2 x 0.75 mm
2
(Shielded cable)
2 x 0.75 mm
2
+ GND
RAS-2.5WHVRP1
12.9
2 x 2.5 mm² + GND
RAS-3WHVRP1
15.8
2 x 4.0 mm² + GND
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.1 - 09/2021
31