6.3 TERMINAL BOARD CONNECTIONS
6.3.1 Table board 1
Main power supply
The main power supply connection is wired to the Terminal board (TB1) as follows:
YUTAKI (S / S COMBI)
x
x
x
x
Operating Line
(Twisted shielded pair cable or
shielded pair cable)
DC5V (Non-Pole Transmission,
H-LINK system)
Outdoor unit
RAS-WHV(N/R)P(1)(E)
YUTAKI S / S COMBI
Outdoor unit
RAS-WHNP(1)E
Operating Line
(Twisted shielded
pair cable or
shielded pair cable)
DC5V (Non-Pole
Transmission,
H-LINK system)
Earth
Earth
Earth
Earth
YUTAKI S / S COMBI
6.3.2 Table board 2
Indoor/outdoor communication wiring (TB2) / ATW-RTU Communication / Central Devices Communication
•
The transmission is wired to terminals 1-2.
•
The H-LINK II wiring system requires only two transmission cables that connect the indoor unit and the outdoor unit in case of split
system and also connect the indoor unit with ATW-RTU or Central devices like ATW-TAG-02, ATW-KNX-02 and ATW-MBS-02.
1
1
2
2
Indoor unit
Outdoor unit ATW-RTU /
Central Devices
•
Use twist pair wires (0.75 mm²) for operation wiring between outdoor unit and indoor unit. The wiring must consist of 2-core wires
(Do not use wire with more than 3 cores).
•
Use shielded wires for intermediate wiring to protect the units from noise interference, with a length of less than 300 m and a size
in compliance with local codes.
•
In the event that a conduit tube for field-wiring is not used, fix rubber bushes to the panel with adhesive.
!
C A U T I O N
Ensure that the transmission wiring is not wrongly connected to any live part that could be damaged the PCB.
Input and output terminals give the possibility to configure the installation according to the needs of the user. The default settings
and I/O terminals reach most of the options necessary for an optimal performance of the system. Additionally, the settings can be
modified through the unit controller, and input/output terminals can be used, if required, to have additional options.
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.1 - 09/2021
36