Removing a fan module
1
.
Put on an anti-static wrist strap.
2
.
Web console login procedure on page 4-3
section.
3
.
Turn on the maintenance mode from web console.
See
Maintenance mode on/off procedure on page 4-10
section.
4
.
Pull the lock tab while unlocking it and then remove the failed fan module.
Figure 5-156 Removing a cooling fan module
Installing a fan module
1
.
Put on an anti-static wrist strap.
2
.
Reverse the removal procedure.
3
.
Turn off the maintenance mode from web console.
See
Maintenance mode on/off procedure on page 4-10
section.
4
.
Verify that the replacement was successful through the MAR log.
See
Alert information identification procedure on page 4-5
section.
Replacing a front panel module
This procedure describes how to replace a front panel module. The front
panel module is a hot-swappable component and allows the front panel
module replacement with the server chassis power on.
Removing a front panel module
1
.
Put on an anti-static wrist strap.
2
.
Web console login procedure on page 4-3
section.
5-124
Replacing parts
Hitachi Compute Blade 500 Series System Service Manual
Summary of Contents for CB 520A A1
Page 26: ...xxvi Preface Hitachi Compute Blade 500 Series System Service Manual ...
Page 152: ...4 64 Common process for replacement Hitachi Compute Blade 500 Series System Service Manual ...
Page 294: ...6 12 Identifying RAID rebuild status Hitachi Compute Blade 500 Series System Service Manual ...
Page 432: ...9 16 Updating firmware Hitachi Compute Blade 500 Series System Service Manual ...
Page 439: ...Change LOM configuration 10 7 Hitachi Compute Blade 500 Series System Service Manual ...
Page 442: ...10 10 Change LOM configuration Hitachi Compute Blade 500 Series System Service Manual ...
Page 450: ...10 18 Change LOM configuration Hitachi Compute Blade 500 Series System Service Manual ...
Page 464: ...11 14 Troubleshooting Hitachi Compute Blade 500 Series System Service Manual ...
Page 465: ...Hitachi Compute Blade 500 Series System Service Manual ...