Step
Symptom
Possible Cause
Actions / Verifications
1
.
Push the Shutdown switch about 4
seconds to power off the suspected
management module.
2
.
Remove the suspected management
module.
3
.
Inspect the connector for damage.
4
.
Install it into the original bay again if
it did not have damaged connector.
Verification 2
1
.
If the Power LED of the suspected
management module starts blink in
green, the repair is completed.
2
.
If the suspected management module
has damaged connector, then go to
step 5.
3
.
If the Power LED remains off, go to
the following Action 3.
Action 3
1
.
Push the Shutdown switch about 4
seconds to power off the suspected
management module.
2
.
Remove the suspected management
module and replace it with the spare
one.
Verification 3
1
.
If the Power LED starts blink in
green, replacing is completed.
2
.
If the Power LED remains off, go to
step 5.
2
•
The Power LED
does not stop
blink in green
for more than
10 minutes.
or
•
The
HEARTBEAT
LED is off or is
solid green (not
blink).
Management
module fault
Action 1
1
.
Push the Shutdown switch about 4
seconds to power off the suspected
management module.
2
.
Wait for one minute.
3
.
Push the Shutdown switch, and then
power it up.
Verification 1
1
.
If the Power LED is solid green after
blink in green, then the repair is
completed.
2
.
If the Power LED is not solid green,
then the following Action 2.
Action 2
1
.
Remove the suspected management
module and replace it the spare one.
Verification 2
1
.
If the Power LED starts blink in
green, replacing is completed.
11-6
Troubleshooting
Hitachi Compute Blade 500 Series System Service Manual
Summary of Contents for CB 520A A1
Page 26: ...xxvi Preface Hitachi Compute Blade 500 Series System Service Manual ...
Page 152: ...4 64 Common process for replacement Hitachi Compute Blade 500 Series System Service Manual ...
Page 294: ...6 12 Identifying RAID rebuild status Hitachi Compute Blade 500 Series System Service Manual ...
Page 432: ...9 16 Updating firmware Hitachi Compute Blade 500 Series System Service Manual ...
Page 439: ...Change LOM configuration 10 7 Hitachi Compute Blade 500 Series System Service Manual ...
Page 442: ...10 10 Change LOM configuration Hitachi Compute Blade 500 Series System Service Manual ...
Page 450: ...10 18 Change LOM configuration Hitachi Compute Blade 500 Series System Service Manual ...
Page 464: ...11 14 Troubleshooting Hitachi Compute Blade 500 Series System Service Manual ...
Page 465: ...Hitachi Compute Blade 500 Series System Service Manual ...