3. Transportation and Handling
3.1 Transportation
Transport the product as close to the installation
location as practicable before unpacking.
3.3 Combination of CH-Box and Indoor Unit
Combination is as follows.
Table 3.1 Combination of Indoor Unit
3.2 Handling of CH-Box
Do not put any foreign material into the indoor
unit and check to ensure that none exists in
the CH-Box before the installation and test run.
Otherwise, a fire or failure, or something similar
may occur.
Do not put any material on the product.
Be careful not to damage insulation materials
of unit’s surface when lifting.
NOTES:
1. Exceeding the total capacity may cause insufficient performance and abnormal sound. Be sure to
connect the CH-Box within the allowable total capacity.
2. In case of 8HP or 10HP type indoor unit connection:
Only single unit per branch is allowed to be connected.
Up to two 8HP or 10HP type indoor units can be connected to the CH-Box within the “Maximum Total
Capacity of All Connected Indoor Units” shown in above table.
Make sure to increase the pipe connection size by using the appropriate accessory pipe.
Model
CH-AP04MSSX
JCH-AP04MSSX
CH-AP08MSSX
JCH-AP08MSSX
CH-AP12MSSX
JCH-AP12MSSX
CH-AP16MSSX
JCH-AP16MSSX
Number of Branches (for Indoor Unit)
4
8
12
16
Single Unit
Per Branch
Maximum Total Capacity of
All Connected Indoor Units
16.0HP or less
(Max. 44.8kW)
30.0HP or less
(Max. 85.0kW)
30.0HP or less
(Max. 85.0kW)
30.0HP or less
(Max. 85.0kW)
Maximum Total Capacity of
Connected Indoor Units Per
Branch
6.0HP or less
(Max. 16.0kW)
6.0HP or less
(Max. 16.0kW)
6.0HP or less
(Max. 16.0kW)
6.0HP or less
(Max. 16.0kW)
Multiple Units
Per Branch
(*1)
Maximum Number of
Connected Indoor Units Per
Branch
6
6
6
6
Maximum Total Capacity of
All Connected Indoor Units
16.0HP or less
(Max. 44.8kW)
30.0HP or less
(Max. 85.0kW)
30.0HP or less
(Max. 85.0kW)
30.0HP or less
(Max. 85.0kW)
Maximum Total Capacity of
Connected Indoor Units Per
Branch
6.0HP or less
(Max. 16.0kW)
6.0HP or less
(Max. 16.0kW)
6.0HP or less
(Max. 16.0kW)
6.0HP or less
(Max. 16.0kW)
(*1) When multiple indoor units are connected to the same branch of CH-Box, they are controlled with the
same operation mode.