Apply by making
contact to the piping.
Check that there are no gaps between
the CH-Box and the insulation.
Apply by making
contact to the piping.
Check that there are no gaps between
the CH-Box and the insulation.
Check that there are no gaps between
the CH-Box and the insulation.
Check there are no gaps between insulation materials.
If the gaps are occurs, seal the gap with vinyl tape.
Securely fasten.
Securely fasten cable clamps
and the vinyl tape (Field-Supplied).
Securely fasten cable clamps
and the vinyl tape (Field-Supplied).
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation
(Accessory (6))
Insulation
(Accessory (5))
Clamp
(Accessory (7))
Securely fasten.
Clamp
(Accessory (7))
Insulation Material
(Attached to the CH-Box)
Insulation Material
(Attached to the CH-Box)
Insulation Material
(Attached to the CH-Box)
Insulation Material
(Attached to the CH-Box)
Insulation Material
(Attached to the CH-Box)
CH-Box Side
CH-Box Side
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation Work for Gas (High/Low Pressure and Low Pressure)
Pipe of Outdoor Unit Side
Insulation Work for Liquid Pipe of Outdoor Unit Side
Insulation Work for Gas Pipe of Indoor Unit Side
Insulation Work for Liquid Pipe of Indoor Unit Side
CH-Box Side
CH-Box Side
P5417025-rev.1
19
(d) In case there are unused piping connection, ensure
to apply accessory insulation material to the piping
and flare connections without gaps as shown on
the right figure. (For gas and liquid sides)
Insulate without gaps.
Insulation
(Accessory (5), (6))
Securely fasten.
Clamp
(Accessory (7))
(b) Insulate gas and liquid pipe separately using the accessory insulation material.
In the event that temperature and humidity levels inside the ceiling exceed 30
°
C (86
o
F)/RH, relative
humidity 80%, apply additional insulation materials (approximately 10mm (3/8 inch) thickness) to the
surface of the accessory insulation material to avoid condensation.
(c) Perform cold insulation work by insulating and taping the flare connection and reducer connection.
Also insulate all the refrigerant pipes.