For Mexico
model only.
Outdoor
1 2
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB1
1
A 2
B
Indoor Unit A
Power Supply Wiring
Outdoor Unit
Power Supply
1~/N 230V/50Hz
1~/N 220-240V/50Hz
1~/N 220V/60Hz
1
A 2
B
Indoor Unit B
1
A 2
B
Indoor Unit L
1
1
A 2
B
Indoor Unit L
2
When multiple indoor units are connected to the same branch of CH-Box,
the operation mode (cooling/heating) for the indoor units will be the same.
1
A 2
B
Cooling Only Indoor Unit
CH-Box
Connect communication
cable from cooling only
indoor unit to the outdoor
terminal block (TB2) in
CH-Box.
Communication Cable
Outdoor Unit
3
2
O.U.-O.U.
4
1
H-LINK
CH-AP04MSSX
TB3
TB4
PCB1
Indoor
4
6
5
3
7 8 9 10
A
B
C
D
Indoor
TB3
TB4
PCB2
Indoor
4
6
5
3
7 8 9 10
E
F
G
H
Indoor
TB3
TB4
PCB3
Indoor
4
6
5
3
7 8 9 10
I
J
K
L
Indoor
Outdoor
1 2
TB2
TB3
TB4
PCB1
Indoor
4
6
5
3
7 8
A
B
C
Indoor
CH-Box
A to L indicate the Indoor Unit number.
WC
WC
WC
WC
WC
CH-AP08MSSX
CH-AP12MSSX
WC: Wired Controller
(Non-Polarity)
(DC5V)
Communication Cable
(Non-Polarity)
(DC5V)
Connect
communication cable
from outdoor unit
to the outdoor
terminal block (TB2)
in CH-Box.
ELB
S
Earth
Leakage
Breaker
Main Switch
and Fuse
Power
Supply
R/
L1
S/
L2
TB3
TB4
PCB4
Indoor
4
6
5
3
7 8 9 10
M
N
O
P
Indoor
CH-AP16MSSX
5
3
3
2
1
4
1~, 208-230V/50Hz
1~, 220V/60Hz
22
P5417025-rev.1
• Example of Electrical Wiring
The following figure shows an example of electrical wiring around the CH-Boxes.
NOTES:
1. Do not apply excessive voltage to the communication cable DC5V (non-polarity) between the outdoor
unit and the CH-Box, between the CH-Box and the indoor unit or between CH-Boxes.
2. Use 2-Conductor shielded communication cable for the communication cable. (Do not use 3-Conductor
cable or over.)
3. Connect the communication cable for the outdoor unit to terminals “1” and “2” on TB2 in the CH-Box.
4. Connect the communication cable for the indoor unit exclusively for cooling operation to the terminal “1”
and “2” on TB2 in the CH-Box.
5. For a CH-Box in the same refrigerant cycle, an electrical power supply can be supplied by one main
switch.
6. Do not connect the power supply line (220-240V/220V/230V) to the terminal block for transmission line.
7. Connect the ground wiring for the outdoor/indoor units and CH-Box. When ground resistance is less
than 100 ohms, ground wiring work should be performed by the qualified electrician.
8. Do not run the communication cables along with power supply wirings in the CH-Box.
Separate communication cables from the power supply wirings.