Second Acceleration and Deceleration Functions
The X200 inverter features two-stage acceleration and deceleration ramps. This gives
flexibility in the profile shape. You can specify the frequency transition point, the point
at which the standard acceleration (F002) or deceleration (F003) changes to the second
acceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] to
trigger this transition. These profile options are also available for the second motor
settings. Select a transition method via A094 as depicted below. Be careful not to
confuse the
second acceleration/deceleration settings with settings for the second motor!
“A” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Acceleration (2) time setting
A092
ACC 2
0015.00s
Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
9
15.00 15.00
sec
Acceleration (2) time setting,
2nd motor
A292
2ACC2
0015.00s
Duration of 2nd segment of
acceleration, 2nd motor, range is:
0.01 to 3000 sec.
9
15.00 15.00
sec
Deceleration (2) time setting
A093
DEC 2
0015.00s
Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
9
15.00 15.00
sec
Deceleration (2) time setting,
2nd motor
A293
2DEC2
0015.00s
Duration of 2nd segment of
deceleration, 2nd motor, range is:
0.01 to 3000 sec.
9
15.00 15.00
sec
Select method to switch to
Acc2/Dec2 profile
A094
ACC CHG
TM
Two options for switching from
1st to 2nd accel/decel:
00
}
2CH input from terminal
01
}
Transition frequency
U
00
00
Select method to switch to
Acc2/Dec2 profile, 2nd motor
A294
2ACCCHG
TM
Two options for switching from
1st to 2nd accel/decel:
00
}
2CH input from terminal
01
}
Transition frequency
(2nd motor)
U
00
00
A094 = 00
Transition via 2CH input
Output
frequency
Accel 1
Accel 2
2CH
input
1
0
t
t
0
A094 = 01
Transition via freq. level
Output
frequency
Accel 1
Accel 2
t
0
A095
Frequency
transition point
3
25
Config
uri
ng Driv
e
Parameters
3
−
25
&RQ¿JXULQJ'ULYH
Parameters